PGS-31 is a proven workhorse design to maximize the availability of critical equipment continuously ensuring that the business process is protected against all power problems. The true online double conversion isolation transformer based design is ideally suited to cater to all types of Industrial and IT applications.
INPUT | |||||||
---|---|---|---|---|---|---|---|
Ratings (KVA / KW) | 10 / 9 | 15 / 13.5 | 20 / 18 | 30 / 27 | 40 / 36 | 50 / 45 | 60 / 54 |
Nominal Voltage | 3ø, 380 / 400 / 415V | ||||||
Voltage Range | 350 to 460 | ||||||
Frequency | 50 or 60 Hz (Selectable) | ||||||
Frequency Range | 40 to 60Hz | ||||||
Current Distortion | <9% (Optional) | ||||||
Power Factor | 0.99 (Optional) | ||||||
OUTPUT | |||||||
Nominal Voltage | 220V / 230V / 240V | ||||||
Frequency | 50 or 60 Hz (Selectable) | ||||||
Power Factor | 0.9 | ||||||
Voltage Regulation | |||||||
Static | ±1% | ||||||
Dynamic | ± 5% | ||||||
Voltage Distortion | < 3% at Linear Load | ||||||
Overload | 125% for 10 minutes | ||||||
Crest factor | 3:1 | ||||||
Efficiency | |||||||
Inverter | 93% | ||||||
Overall | 91% | ||||||
DC LINK | |||||||
Battery Voltage | 384 Volts | ||||||
Voltage Tolerance | ± 1% | ||||||
Voltage Ripple | < ± 1% | ||||||
STATIC BYPASS | |||||||
Switching time | |||||||
Inverter Failure | 2 ms | ||||||
Other Modes | 0 | ||||||
ENVIRONMENTAL CONDITION | |||||||
Operating temperature | 0-40°C | ||||||
Storage Temperature | -20°C to +70°C (Not for Batteries) | ||||||
Relative Humidity | 95% Non-condensing | ||||||
Maximum altitude above sea level | 1000 meters without derating | ||||||
PHYSICAL | |||||||
Dimensions (W × D × H mm) | 390 × 910 × 630 | 530 × 920 × 860 | 810 × 870 × 1850 | ||||
Approx. Weight (kg.) | 200 | 250 | 300 | 350 | 380 | 500 | 600 |
GENERAL | |||||||
Ingress protection | IP – 20 | ||||||
Audible noise at 1 meter | < 60dBA | < 65dBA | |||||
Cooling | Forced air |